quotation:[Copy]
Jan Erik STELLET,Tobias ROGG2.[en_title][J].Control Theory and Technology,2014,12(4):345~356.[Copy]
【Print page】 【Online reading】【Download 【PDF Full text】 View/Add CommentDownload reader Close

←Previous page|Page Next →

Back Issue    Advanced search

This Paper:Browse 1583   Download 1235 本文二维码信息
码上扫一扫!
On linear observers and application to fault detection in synchronous generators
JanErikSTELLET,TobiasROGG2
0
(Karlsruhe Institute of Technology)
摘要:
This work introduces an observer structure and highlights its distinct advantages in fault detection and isolation. Its application to the issue of shorted turns detection in synchronous generators is demonstrated. For the theoretical foundation, the convergence and design of Luenberger-type observers for disturbed linear time-invariant (LTI) single-input single-output (SISO) systems are reviewed with a particular focus on input and output disturbances. As an additional result, a simple observer design for stationary output disturbances that avoids a system order extension, as in classical results, is proposed.
关键词:  Synchronous generators  Field winding  Fault detection  Unknown input observer (UIO)  Disturbance observer  Residual generation
DOI:
Received:March 07, 2013Revised:October 11, 2014
基金项目:
On linear observers and application to fault detection in synchronous generators
Jan Erik STELLET,Tobias ROGG2
(Karlsruhe Institute of Technology;Swiss Federal Institute of Technology)
Abstract:
This work introduces an observer structure and highlights its distinct advantages in fault detection and isolation. Its application to the issue of shorted turns detection in synchronous generators is demonstrated. For the theoretical foundation, the convergence and design of Luenberger-type observers for disturbed linear time-invariant (LTI) single-input single-output (SISO) systems are reviewed with a particular focus on input and output disturbances. As an additional result, a simple observer design for stationary output disturbances that avoids a system order extension, as in classical results, is proposed.
Key words:  Synchronous generators  Field winding  Fault detection  Unknown input observer (UIO)  Disturbance observer  Residual generation